Deck 5: Conductor Identification, Switch Control of Lighting Circuits, Bondinggrounding of Wiring Devices, Induction Heating

Full screen (f)
exit full mode
Question
Screwless push-in terminals (i.e., back wiring holes) on receptacles are listed only for use with what type of branch-circuit conductor?
Use Space or
up arrow
down arrow
to flip the card.
Question
On isolated ground receptacles, the metal yoke ____ integrally bonded to the equipment grounding terminal of the receptacle.

A) is
B) is not
Question
When using individual conductors in raceway, which insulation color is NOT permitted for the grounded conductor (neutral)?

A) gray
B) white
C) green with three white stripes
Question
Snap switches with nonmetallic yokes (straps) have a terminal for the equipment grounding conductor. Using this type of switch provides a means for grounding ____ faceplates when nonmetallic boxes are used.

A) oversize (goof)
B) metal
C) nonmetallic
D) recessed
Question
"T"-rated snap switches are intended for what application?
Question
The grounded (identified) conductor of 6 AWG or smaller must have an outer finish that is ____.

A) white
B) gray
C) three continuous white stripes
D) any of the above
Question
When receptacles or switches have No. 6-32 screws secured to them with small pieces of cardboard, these pieces of cardboard must be ____ when the wiring device is installed in a metal outlet box.

A) left in place
B) removed
C) replaced with metal lock washers
D) none of these
Question
From how many locations does four-way switching allow a lighting outlet to be controlled?
Question
Describe what NEC 250.148 requires to maintain the continuity of the equipment grounding path.
Question
Name at least four kinds of lighting switches.
Question
When terminating a receptacle, the white (grounded) conductor is always connected to the ____________________-colored terminal, and the phase (hot) conductor is always connected to the ____________________-colored terminal.
Question
The conductors that run between a switched outlet and the switch controlling the outlet are called a(n) ____________________.
Question
Phase conductors 6 AWG and smaller ____ permitted to be re-identified as equipment ground conductors using green paint, tape, or other effective means.

A) are
B) are not
Question
The NEC requires that switching be done only in ____ conductors.

A) ungrounded
B) designated
C) black
D) red
Question
When is a reidentified white conductor NOT permitted?
Question
In older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a conductive floor such as tile or cement, NEC 404.9(B) requires the use of what kind of faceplate?
Question
To avoid inductive heating in metallic raceways, the NEC requires that ____.

A) all circuit conductors be run in the same raceway
B) the grounded (neutral) conductor be oversized
C) the equipment grounding conductor be bonded to the raceway
D) none of these
Question
All 125-volt, 15- and 20-ampere receptacles in a dwelling are required to be ____.

A) tamper resistant
B) AFCI protected
C) GFCI protected
D) weather resistant
Question
Alternating current, general-use snap switches are UL-listed to control motors rated up to ____ horsepower.

A) 1/2
B) 3/4
C) 2
D) as marked on the switch
Question
The long slot on a 15-ampere, 125-volt, receptacle is the ____ conductor.

A) grounded
B) phase "hot"
C) equipment-grounding
D) traveler
Question
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
14 AWG copper
Question
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
12 AWG copper
Question
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
10 AWG copper
Question
Receptacles have several screw terminals for the attachment of circuit conductors. Match the following screws with their intended conductor.
a.Equipment grounding conductor
b.Hot (phase) conductor
c.Grounded (white) conductor
Silver-colored screw
Question
Match the following switch types with the correct number of terminals for each.
a.Two terminals
b.Four terminals
c.Three terminals
Three-way switch
Question
Receptacles have several screw terminals for the attachment of circuit conductors. Match the following screws with their intended conductor.
a.Equipment grounding conductor
b.Hot (phase) conductor
c.Grounded (white) conductor
Green hexagonal screw
Question
Match the following switch types with the correct number of terminals for each.
a.Two terminals
b.Four terminals
c.Three terminals
Four-way switch
Question
A 4-way switch does not have "ON" and "OFF" markings. Four-way switches are connected to the "____________________" between two 3-way switches. One 3-way switch is fed by the ____________________; the other 3-way switch is connected to the load.
Question
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
The common point on a wye-connected polyphase system or the mid-point on a single phase system is the _________________________.
Question
Match the following switch types with the correct number of terminals for each.
a.Two terminals
b.Four terminals
c.Three terminals
Single-pole switch
Question
Receptacles have several screw terminals for the attachment of circuit conductors. Match the following screws with their intended conductor.
a.Equipment grounding conductor
b.Hot (phase) conductor
c.Grounded (white) conductor
Brass-colored screw
Unlock Deck
Sign up to unlock the cards in this deck!
Unlock Deck
Unlock Deck
1/31
auto play flashcards
Play
simple tutorial
Full screen (f)
exit full mode
Deck 5: Conductor Identification, Switch Control of Lighting Circuits, Bondinggrounding of Wiring Devices, Induction Heating
1
Screwless push-in terminals (i.e., back wiring holes) on receptacles are listed only for use with what type of branch-circuit conductor?
These terminals are used with solid 14 AWG copper conductors.
2
On isolated ground receptacles, the metal yoke ____ integrally bonded to the equipment grounding terminal of the receptacle.

A) is
B) is not
B
3
When using individual conductors in raceway, which insulation color is NOT permitted for the grounded conductor (neutral)?

A) gray
B) white
C) green with three white stripes
C
4
Snap switches with nonmetallic yokes (straps) have a terminal for the equipment grounding conductor. Using this type of switch provides a means for grounding ____ faceplates when nonmetallic boxes are used.

A) oversize (goof)
B) metal
C) nonmetallic
D) recessed
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
5
"T"-rated snap switches are intended for what application?
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
6
The grounded (identified) conductor of 6 AWG or smaller must have an outer finish that is ____.

A) white
B) gray
C) three continuous white stripes
D) any of the above
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
7
When receptacles or switches have No. 6-32 screws secured to them with small pieces of cardboard, these pieces of cardboard must be ____ when the wiring device is installed in a metal outlet box.

A) left in place
B) removed
C) replaced with metal lock washers
D) none of these
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
8
From how many locations does four-way switching allow a lighting outlet to be controlled?
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
9
Describe what NEC 250.148 requires to maintain the continuity of the equipment grounding path.
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
10
Name at least four kinds of lighting switches.
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
11
When terminating a receptacle, the white (grounded) conductor is always connected to the ____________________-colored terminal, and the phase (hot) conductor is always connected to the ____________________-colored terminal.
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
12
The conductors that run between a switched outlet and the switch controlling the outlet are called a(n) ____________________.
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
13
Phase conductors 6 AWG and smaller ____ permitted to be re-identified as equipment ground conductors using green paint, tape, or other effective means.

A) are
B) are not
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
14
The NEC requires that switching be done only in ____ conductors.

A) ungrounded
B) designated
C) black
D) red
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
15
When is a reidentified white conductor NOT permitted?
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
16
In older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a conductive floor such as tile or cement, NEC 404.9(B) requires the use of what kind of faceplate?
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
17
To avoid inductive heating in metallic raceways, the NEC requires that ____.

A) all circuit conductors be run in the same raceway
B) the grounded (neutral) conductor be oversized
C) the equipment grounding conductor be bonded to the raceway
D) none of these
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
18
All 125-volt, 15- and 20-ampere receptacles in a dwelling are required to be ____.

A) tamper resistant
B) AFCI protected
C) GFCI protected
D) weather resistant
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
19
Alternating current, general-use snap switches are UL-listed to control motors rated up to ____ horsepower.

A) 1/2
B) 3/4
C) 2
D) as marked on the switch
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
20
The long slot on a 15-ampere, 125-volt, receptacle is the ____ conductor.

A) grounded
B) phase "hot"
C) equipment-grounding
D) traveler
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
21
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
14 AWG copper
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
22
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
12 AWG copper
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
23
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
10 AWG copper
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
24
Receptacles have several screw terminals for the attachment of circuit conductors. Match the following screws with their intended conductor.
a.Equipment grounding conductor
b.Hot (phase) conductor
c.Grounded (white) conductor
Silver-colored screw
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
25
Match the following switch types with the correct number of terminals for each.
a.Two terminals
b.Four terminals
c.Three terminals
Three-way switch
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
26
Receptacles have several screw terminals for the attachment of circuit conductors. Match the following screws with their intended conductor.
a.Equipment grounding conductor
b.Hot (phase) conductor
c.Grounded (white) conductor
Green hexagonal screw
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
27
Match the following switch types with the correct number of terminals for each.
a.Two terminals
b.Four terminals
c.Three terminals
Four-way switch
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
28
A 4-way switch does not have "ON" and "OFF" markings. Four-way switches are connected to the "____________________" between two 3-way switches. One 3-way switch is fed by the ____________________; the other 3-way switch is connected to the load.
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
29
Specify the maximum overcurrent protection permitted for following the circuit conductor sizes:
a.15 amperes
b.20 amperes
c.30 amperes
The common point on a wye-connected polyphase system or the mid-point on a single phase system is the _________________________.
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
30
Match the following switch types with the correct number of terminals for each.
a.Two terminals
b.Four terminals
c.Three terminals
Single-pole switch
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
31
Receptacles have several screw terminals for the attachment of circuit conductors. Match the following screws with their intended conductor.
a.Equipment grounding conductor
b.Hot (phase) conductor
c.Grounded (white) conductor
Brass-colored screw
Unlock Deck
Unlock for access to all 31 flashcards in this deck.
Unlock Deck
k this deck
locked card icon
Unlock Deck
Unlock for access to all 31 flashcards in this deck.