Deck 2: Types of Certification Required for the Inspecting and Testing of Electrical

ملء الشاشة (f)
exit full mode
سؤال
What is the status of the person who is carrying out an inspection and test

A) Duty holder
B) Electrician
C) Competent
D) Qualified
استخدم زر المسافة أو
up arrow
down arrow
لقلب البطاقة.
سؤال
Which of the following documents is non statutory

A) Electricity at work regulations 1989
B) Health and safety at work regulations 1974
C) Electrical safety quality and continuity regulations 2002
D) GS 38
سؤال
The correct document required when an electrical installation has been overloaded is

A) An electrical installation certificate
B) A minor works certificate
C) An electrical installation condition report
D) A periodic inspection report
سؤال
A periodic inspection need not be carried out when

A) It is too expensive
B) Regular documented maintenance is carried out
C) The due date has expired
D) The installation is more than 10 years old
سؤال
A low resistance ohmmeter must produce a voltage of

A) 50v
B) 500v
C) 2 - 24v
D) 2 - 24mV
سؤال
A test instrument which could be used to measure the resistance of an earth electrode is

A) A low resistance ohm meter
B) An earth fault loop impedance tester
C) A prospective short circuit current tester
D) An insulation resistance tester
سؤال
Why is it important that the tests carried out during an initial verification carried out in the correct order

A) To save time
B) To avoid excessive battery use
C) Safety
D) It is easy to remember
سؤال
The calculation for circuit earth fault loop impedance is

A) Zs = Ze + R1 + R2
B) Ze = Zs - R1 + R2
C) Zs = Ze + R1 + Rn
D) Ze = Zs + R1 + R2
سؤال
A conductor which is 36 m long has a resistance of 7.41mΩ per meter calculate its end to end resistance

A) 0.26mΩ
B) 2.66Ω
C) 0.26Ω
D) 2.66mΩ
سؤال
The circuits in an installation have an insulation resistance of 20MΩ, 34MΩ 18MΩ and 20MΩ if the insulation resistance was measured from the meter tails the expected insulation resistance would be

A) 5.40MΩ
B) 546MΩ
C) 5.46Ω
D) 5.46mΩ
سؤال
The test which must be carried out prior to the RCD test during a periodic inspection is

A) Push button test
B) Prospective short circuit current
C) Earth fault loop impedance
D) Insulation resistance
سؤال
The tests currents required when testing a 300mA RCD are

A) 150mA, 300mA and 1500mA
B) 15mA, 30mA and 150mA
C) 0.15A, 0.3A
D) 0.015A 0.030A
سؤال
The first three tests required for an initial verification are

A) Polarity, Insulation resistance and earth fault loop
B) Continuity of protective conductors, polarity and insulation resistance
C) Ring final circuit test, insulation resistance and earth fault loop impedance
D) Continuity of protective conductors, ring final circuit test and insulation resistance
سؤال
The maximum rating of an RCD used for fire protection is

A) 300mA
B) Time delayed 300mA
C) Time delayed 30mA
D) 500mA
سؤال
The correct IP rating for equipment installed in Zone 2 of a bathroom is

A) IP4X
B) IPXXB
C) IPX4
D) IPX2
سؤال
The IP rating used to indicate finger protection is

A) IP2X
B) IPXXB
C) IP4X
D) IPXXD
سؤال
The current which should cause automatic disconnection of a 20a type B BS EN 60898 circuit breaker is

A) 100A
B) 200A
C) 100mA
D) 21A
سؤال
The stated maximum Ze for a TN-S supply system is

A) 0.35Ω
B) 0.21Ω
C) 0.8Ω
D) 0.85Ω
سؤال
A TT system is normally an

A) Overhead supply
B) Underground supply
C) Generator supply
D) A top to tail supply
سؤال
Ipf is the symbol used for the value of

A) Current power factor
B) Current, power and frequency
C) Frequency of phase current
D) Prospective fault current
فتح الحزمة
قم بالتسجيل لفتح البطاقات في هذه المجموعة!
Unlock Deck
Unlock Deck
1/20
auto play flashcards
العب
simple tutorial
ملء الشاشة (f)
exit full mode
Deck 2: Types of Certification Required for the Inspecting and Testing of Electrical
1
What is the status of the person who is carrying out an inspection and test

A) Duty holder
B) Electrician
C) Competent
D) Qualified
A
2
Which of the following documents is non statutory

A) Electricity at work regulations 1989
B) Health and safety at work regulations 1974
C) Electrical safety quality and continuity regulations 2002
D) GS 38
D
3
The correct document required when an electrical installation has been overloaded is

A) An electrical installation certificate
B) A minor works certificate
C) An electrical installation condition report
D) A periodic inspection report
D
4
A periodic inspection need not be carried out when

A) It is too expensive
B) Regular documented maintenance is carried out
C) The due date has expired
D) The installation is more than 10 years old
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
5
A low resistance ohmmeter must produce a voltage of

A) 50v
B) 500v
C) 2 - 24v
D) 2 - 24mV
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
6
A test instrument which could be used to measure the resistance of an earth electrode is

A) A low resistance ohm meter
B) An earth fault loop impedance tester
C) A prospective short circuit current tester
D) An insulation resistance tester
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
7
Why is it important that the tests carried out during an initial verification carried out in the correct order

A) To save time
B) To avoid excessive battery use
C) Safety
D) It is easy to remember
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
8
The calculation for circuit earth fault loop impedance is

A) Zs = Ze + R1 + R2
B) Ze = Zs - R1 + R2
C) Zs = Ze + R1 + Rn
D) Ze = Zs + R1 + R2
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
9
A conductor which is 36 m long has a resistance of 7.41mΩ per meter calculate its end to end resistance

A) 0.26mΩ
B) 2.66Ω
C) 0.26Ω
D) 2.66mΩ
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
10
The circuits in an installation have an insulation resistance of 20MΩ, 34MΩ 18MΩ and 20MΩ if the insulation resistance was measured from the meter tails the expected insulation resistance would be

A) 5.40MΩ
B) 546MΩ
C) 5.46Ω
D) 5.46mΩ
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
11
The test which must be carried out prior to the RCD test during a periodic inspection is

A) Push button test
B) Prospective short circuit current
C) Earth fault loop impedance
D) Insulation resistance
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
12
The tests currents required when testing a 300mA RCD are

A) 150mA, 300mA and 1500mA
B) 15mA, 30mA and 150mA
C) 0.15A, 0.3A
D) 0.015A 0.030A
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
13
The first three tests required for an initial verification are

A) Polarity, Insulation resistance and earth fault loop
B) Continuity of protective conductors, polarity and insulation resistance
C) Ring final circuit test, insulation resistance and earth fault loop impedance
D) Continuity of protective conductors, ring final circuit test and insulation resistance
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
14
The maximum rating of an RCD used for fire protection is

A) 300mA
B) Time delayed 300mA
C) Time delayed 30mA
D) 500mA
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
15
The correct IP rating for equipment installed in Zone 2 of a bathroom is

A) IP4X
B) IPXXB
C) IPX4
D) IPX2
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
16
The IP rating used to indicate finger protection is

A) IP2X
B) IPXXB
C) IP4X
D) IPXXD
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
17
The current which should cause automatic disconnection of a 20a type B BS EN 60898 circuit breaker is

A) 100A
B) 200A
C) 100mA
D) 21A
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
18
The stated maximum Ze for a TN-S supply system is

A) 0.35Ω
B) 0.21Ω
C) 0.8Ω
D) 0.85Ω
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
19
A TT system is normally an

A) Overhead supply
B) Underground supply
C) Generator supply
D) A top to tail supply
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
20
Ipf is the symbol used for the value of

A) Current power factor
B) Current, power and frequency
C) Frequency of phase current
D) Prospective fault current
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.
فتح الحزمة
k this deck
locked card icon
فتح الحزمة
افتح القفل للوصول البطاقات البالغ عددها 20 في هذه المجموعة.